Design No. P521

Restrained Assembly Rating - 1 and 1-1/2 hr. -(See Items 5, 5A and 5B)

Unrestrained Assembly Rating – 1 and 1-1/2 hr. and 2 hr. – (See Items 5, 5A, and 5B)

1.        Structural Steel Members* - Pre-fabricated light gauge steel truss system consisting of cold-formed, galvanized steel chord and web sections.  Trusses fabricated in various sizes, depths, and from various steel thickness.  Trusses spaced a max. of 48 in. OC.

MiTek Industries, Inc.- Ultra-Span®, Pre-fabricated Light Gauge Steel Truss System

Engineering, fabrication & installation by: Superior Truss & Panel, Inc.  2204 West 159th Street,        Markham, Illinois 60426  Contract:  Bill Welty   708-339-1200

2.  Bridging – (not shown) – Location of lateral bracing for truss chord and web sections to be specified on truss engineering.

3.  Steel Roof Deck – (classified or unclassified) – Corrugated or fluted steel form units, min 22 MSG painted or galv steel, welded or mechanically fastened max. 12 in. OC to truss top chord.

3b. - As an alternative to item 3 - min. 25 MSG, 15/16 in. deep, painted, or galv. units welded or mechanically fastened max. 12 in. OC to the top chord of trusses (item 1). When used, max hourly rating is reducted to 1 hour.  Loadmaster Systems, Inc. - Type HD, ED or PS.

4.  Cementitious Backer Units* - Nom ˝ or 5/8 in. thick sheets. End joints to occur over crests of steel roof deck with end-joints staggered in adjacent rows.  Units loosely laid, adhered or mechanically attached to steel roof deck.

      United States Gypsum Co. – Durock      

      Exterior Cement Board or Durock Cement Board

4A. Wallboard, Gypsum – (classified or unclassified) – (not shown) As an alternative to item 4, Gypsum sheathing, min ˝ in. thick, applied perpendicular to steel roof deck.  End joints to occur over crests of steel roof deck.  Sheathing loosely laid, adhered or mechanically attached to steel roof deck 

5.  Roof Insulation – Foamed Plastic* - Any polyisocyanurate foamed plastic insulation boards bearing the UL classification marking. Min thickness is 1 in. for the 1 hr assembly ratings, and 2 in. for the 1-1/2 hr assembly ratings with no limit on max overall thickness.  Boards installed over the Cementitious backer units (item 4) or gypsum sheathing (item 4A), with the end-joints staggered in adjacent rows. When applied in more than one layer, each layer of board to be offset in both directions from layer below in order to lap all joints.  Boards loosely laid, adhered  or mechanically fastened to Cementitious backer units or gypsum sheathing, and to steel roof deck (item 3).  See foamed plastic (CCVW) category in the fire resistance directory.

5A. Roof insulation - foamed plastic* - (not shown) – As an alternative to item 5 – Any Polystyrene foamed plastic insulation boards bearing the UL classification marking.  Min thickness is 1 in. for the 1hr assembly rating, and 2 in. for the 1-1/2 hr assembly ratings with no limit on max overall thickness.  Boards installed over the Cementitious backer units (item 4) or gypsum sheathing (item 4A), with end –joints staggered in adjacent rows.  When applied in more than one layer, each layer of board to be offset in both directions from layer below in order to lap all joints.  Boards loosely laid, adhered or mechanically fastened to cementitious backer units of gypsum sheathing, and to steel roof deck (item 3).  See foamed plastic (BRYX) category in the Building Materials Directory or Foamed Plastic (CCVW) category in the Fire Resistance Directory.

5B. Roof Insulation – Mineral and Fiber Boards* - (not shown) – As an alternate to Item 5 – Mineral wool, glass fiber or perlite insulation boards, 24 by 48 in. min size, applied in one or more layers.  Min thickness is 1 in. for the 1-hr assembly rating and 2 in. for the 1-1/2 hr assembly ratings with no limit on max overall thickness. Boards loosely laid, adhered or mechanically fastened to cementitious backer units of gypsum sheathing, and to steel roof deck (item 3).  See mineral and fiber boards (BQXR) category in the Building Materials Directory or Mineral and Fiber Boards (CERZ) category in the Fire Resistance Directory.

6.  Roof Covering *- Consisting of hot-mopped or cold – application materials compatible with insulation described herein which provide class A, B, or C coverings.  See Roofing Materials and Systems Directory - Roof Covering Materials (TEVT).

6A. Roofing Membrane * - (not shown) – In lieu of item 6, single ply membrane that is either ballasted, adhered, or mechanically attached to the insulation described herein as permitted under the respective company’s classification.  See Fire Resistance Directory – Roofing Membranes (CHCI) category.

6B.  Metal Roof Deck Panels * - In lieu of or in addition to items 6 and 6A, the roof covering may consist of mechanically fastened galv or painted steel roof deck panels.  Panels may be installed above a steel purlin assembly per metal roof deck manufacturer’s specifications.   Steel purlin assembly to be installed transverse to steel roof trusses (item 1).  A line of sealant or tape may be used at panel side and end laps.  See Metal Roof Deck Panels category in the Roofing Materials and Systems Directory (TJPV) or Fire Resistance Directory (CETW) for names of manufacturers.

 7.  Resilient Channels  Formed of 25 MSG galv steel, installed perpendicular to the trusses (item 1), spaced a max. Of 16 in. OC.  Channels orientated opposite at wallboard butt-joints.  Channel splices overlapped 4 in. beneath steel trusses.  Channels secured to each truss with type S12 by 1/2 in. long screws.  

 7A. Furring Channels - (not shown) -  As an alternate to item 6 Resilient Channels - Min 20 MSG galv. steel, min 2 5/8 in. wide by min 7/8 in. deep, installed perpendicular to the trusses (item 1) spaced a max of 16 in. OC. Two courses of resilient channel positioned 6 in. OC at wallboard butt joints (3 in. from each end of wallboard). Channel splices overlapped 6 in. beneath steel trusses. Channels secured to each truss with No. 18 SWG steel wire double strand saddle ties. Channels tied together with double strand of No. 18 SWG galv. steel wire at each end of overlap.

7B. Resilient Channels - As an alternate to item 6 Resilient Channels, double legged formed of 25 MSG galv. steel 2 7/8 in. deep, spaced 16 in. OC, perpendicular to steel trusses. Two courses of resilient channel positioned 6 in. OC at wallboard butt joints (3 in. from each end of wallboard). Channel splices overlapped 4 in. beneath steel trusses. Channels secured to each truss with Type S12 by 1/2 in. long screws or with No. 18 SWG steel wire double strand saddle ties. Channels tied together with double strand of No. 18 SWG galv. steel wire at each end of overlap..

8.  Wallboard, Gypsum * - For all Ratings except the 2 Hour Ratings - One Layer of nom 5/8 in. thick by 48 in. wide boards, installed with long dimension parallel to trusses.  Attached to the resilient channels using 1 in. long type S bugle head screws spaced 12 in. OC along butted end-joints and 12 in. OC in the field. For the 2 Hour Rating - Two layers of nom. 5/8 in. thick by 48 in. wide boards installed with long dimension parallel to trusses. Base layer attached as described above. ace layer attached to the resilient channels using 1 5/8 in. long Type S bugle head screws spaced 12 in. OC along butt end joints and 12 in. OC in the field. Screws staggered from base layer screws. Face layer side and end joints offset a minimum 16 in. from base layer side and end joints.

            Canadian Gypsum Company –Type C or IP – X2

            United States Gypsum Company – Type C or IP-X2

9.  Finishing System -  (not shown) -  Vinyl, dry or premixed joint compound, applied in two coats to joints and screw heads;  paper tape, 2 in. wide, embedded in first layer of compound over all joints.

* Bearing the UL Classification Marking